Olympia UDM-100W12-UVC-DL Linear UVC LED Strip PASSED UL 2043 Plenum Rating

The Test Samples were exposed to a  60-kW propane burner (see pictures below), and the data recorded included Smoke Release Rate (SRR), Heat Release Rate (HRR) and Total Smoke Release (TSR).

Below are the test results and the PASS judgment:

Below are the Acceptance Criteria:

  1. 1. The peak rate of heat release (HRRs) measured during each test shall be 100 kilowatts or less. The result is 11KW & 12KW (about one-tenth the allowed HRR)
  2. 2. The peak smoke release rate measured during each test shall be 0.21 m2/s or less, SRRs. The result is 0.08 & 0.10 m2/s (less than half the allowed SRR)

3. The total smoke release (10-minute test duration) shall be 75 m2 or less, TSR. The result is 4 & 8 m2  (about one-tenth the allowed TSR)

 Overall the results show OLYMPIA’s Linear UVC LED Strip is very safe for operation in a sealed plenum even under extreme conditions.